No Cool Call. Outdoor Unit Tripping on High Pressure EP183
In this video I found the outdoor unit's fan was not cycling properly and the compressor was going in thermal overload.
Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provides a small commission and helps me make more videos like this one. Thanks for the support!
amazon.com/shop/nighthawkhvac
Follow me on...
nighthawkhvac
nighthawk_hvac
Intro and Outro Music
"Alive" by CHOIX
#nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #trane #varitrac #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump #highpressuretrip#bloweralwayrunning #sparkignitor #ICM #reversingvalve #daikinac #daikinac #ftxs #daikinac #ductless #lowambient #PTAC #Amana #crackedheatexchanger #compromisedheatexchanger #goodman #ECMblowermotor #PSCblowermotor #testo #testo550s #550s #nestthermostat
#nest #daikinac #daikin#doas
Переглядів: 215

Відео

Wera Hex Plus Imperial L Keys Review EP182
Переглядів 231День тому
Can you use the Wera Hex Plus L Key Set in HVAC? Well I asked myself that same question. I bought these in February 2024 and I have been using them now for about 5 months. I'll unbox them, use them in the field, and review them so you can decide if these tools are right for you. If you want a set be sure to pick them up from my amazon store. a.co/d/095Z8hM4 Wera 05022640001 950/9 Hex-Plus Multi...
LG Mini Split Thermostat Will Not Power On EP181
Переглядів 45814 днів тому
So I'm back at the apartment with the push fitting leaks but that's actually not the issue today. At least for this apartment. The thermostat is not powering on. The indoor head is none responsive. The maintenance guy tells me there is voltage present at the indoor head. I checked the breaker, the disconnect and found voltage. Turns out the condensate pump had opened the overflow switch which c...
Kitchen is Too Hot! Low Ambient Controller Problems EP180
Переглядів 1,2 тис.28 днів тому
In this video I came across the kitchen unit was not cooling the space properly. I found the outdoor unit's fan motor was not cycling properly and was short cycling due to a high pressure Trip. Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provides a small commission and helps me make more videos like this one. Thanks for the support! amazon.com/shop/nigh...
Water Source Heat Pump Not Heating EP179
Переглядів 511Місяць тому
The thermostat was not responding. When I removed the batteries I found there was no low voltage. I found the breaker was tripped and I performed a visual inspection and found the run capacitor for the blower motor had fallen out of its holder and shorted to the casing. Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provides a small commission and helps me...
Diagnosing and Replacing a Faulty Defrost Board on a Heat Pump EP178
Переглядів 773Місяць тому
I had a no cool call on this heat pump. Turned out to be a tripped high pressure switch and a faulty defrost board. I installed a universal defrost board and that fixed the issue. Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provides a small commission and helps me make more videos like this one. Thanks for the support! amazon.com/shop/nighthawkhvac Foll...
How to Diagnose a Grounded Compressor EP177
Переглядів 730Місяць тому
In this video I go over the process of checking a compressor to ground. I also go over what details you need to collect to order a new compressor and start components. Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provides a small commission and helps me make more videos like this one. Thanks for the support! amazon.com/shop/nighthawkhvac Follow me on... ...
Heat Pump Not Cooling EP176
Переглядів 1,4 тис.2 місяці тому
In this video I came across this package unit heat pump that had blown the low voltage breaker. I couldn't find the source of the trip but I sure found some issues. The blower was nasty. The indoor coil was nasty, the filters were nasty. All in all the unit was nasty. Join me in this video to get this nasty unit to run. Like the tools I use? Help support the channel. Purchasing tools from my Am...
Burners Go Out After 7 Seconds and It's Not The Flame Sensor EP175
Переглядів 1,1 тис.2 місяці тому
In this video I came across this old Lennox gas fired furnace that would not stay lit. After cleaning the flame sensor it still wouldn't stay lit. Turns out it had a faulty pressure switch. I'll show you how I tested to verify this issue. I also will show you how to install a universal pressure switch. Like the tools I use? Help support the channel. Purchasing tools from my Amazon Store provide...
1980's Lennox Heat Pump Keeps Tripping The Breakers EP174
Переглядів 7132 місяці тому
1980's Lennox Heat Pump Keeps Tripping The Breakers EP174
VAV Not Cooling EP173
Переглядів 9792 місяці тому
VAV Not Cooling EP173
Daikin DOAS Is Having Combustion Issues EP172
Переглядів 8853 місяці тому
Daikin DOAS Is Having Combustion Issues EP172
Heat Pump Outdoor Fan Not Coming On EP171
Переглядів 9083 місяці тому
Heat Pump Outdoor Fan Not Coming On EP171
Two Head Mitsubishi Minisplit Is Having Comm Issues EP170
Переглядів 6313 місяці тому
Two Head Mitsubishi Minisplit Is Having Comm Issues EP170
Nest E Thermostats Not Powering On EP169
Переглядів 6463 місяці тому
Nest E Thermostats Not Powering On EP169
Carrier Package Unit Ignition Failure Dirty Crossover Tubes EP168
Переглядів 5133 місяці тому
Carrier Package Unit Ignition Failure Dirty Crossover Tubes EP168
No Heat! Nasty Filters, a Failed Blower Wheel, and Motor. EP167
Переглядів 4584 місяці тому
No Heat! Nasty Filters, a Failed Blower Wheel, and Motor. EP167
Bosch Inverter System Not Heating EP166
Переглядів 1,3 тис.4 місяці тому
Bosch Inverter System Not Heating EP166
How to Operate The Honeywell HZ432 Zone Control Board EP165
Переглядів 4,9 тис.4 місяці тому
How to Operate The Honeywell HZ432 Zone Control Board EP165
Two Package Units not Heating. Frozen Gas Regulator and Bad Ignitor. EP164
Переглядів 6905 місяців тому
Two Package Units not Heating. Frozen Gas Regulator and Bad Ignitor. EP164
Water Source Heat Pumps Keep Locking Out EP163
Переглядів 1,2 тис.5 місяців тому
Water Source Heat Pumps Keep Locking Out EP163
No Heat. Inducer Draft Motor Not Running EP162
Переглядів 1,9 тис.5 місяців тому
No Heat. Inducer Draft Motor Not Running EP162
Klein Tools KNECT Small Pass-Through Socket Wrench Set 65300 Review EP161
Переглядів 6 тис.6 місяців тому
Klein Tools KNECT Small Pass-Through Socket Wrench Set 65300 Review EP161
VAV's Electric Heat Not Heating EP160
Переглядів 1,9 тис.6 місяців тому
VAV's Electric Heat Not Heating EP160
Gas Fired Heat Exchanger Basics EP159
Переглядів 9197 місяців тому
Gas Fired Heat Exchanger Basics EP159
How to Perform Maintenance on a Trane Self-Contained Intellipak EP158
Переглядів 8907 місяців тому
How to Perform Maintenance on a Trane Self-Contained Intellipak EP158
Trane Veritrac Navigation and Changing Airflow Settings EP157
Переглядів 4788 місяців тому
Trane Veritrac Navigation and Changing Airflow Settings EP157
Economizer Call Turns Into 3 RTU High Limit Trips EP156
Переглядів 9698 місяців тому
Economizer Call Turns Into 3 RTU High Limit Trips EP156
No Cool. Heat Pump With Equalized Pressures.EP155
Переглядів 1,4 тис.8 місяців тому
No Cool. Heat Pump With Equalized Pressures.EP155
Circuit 2 Compressor Keeps Tripping on a Trane Self-Contained Intellipak EP154
Переглядів 1,9 тис.8 місяців тому
Circuit 2 Compressor Keeps Tripping on a Trane Self-Contained Intellipak EP154

КОМЕНТАРІ

  • @soundgineering4771
    @soundgineering4771 2 дні тому

    I think M1 is Common and M6 +24V. Well as long as you have them wired correctly at the zone board side. You can check which wire is common and +24V using a voltmeter by checking first both wires at the meter and then one with the meter and one to the ground.

  • @christopherprince3332
    @christopherprince3332 3 дні тому

    I stopped watching at 13:45 when you put the torch on the pressurized container. OMFG! I have no words.

  • @raddadization
    @raddadization 4 дні тому

    Dang, people still work with R22? I would've just sold a new system esp putting in old refrigerant.

  • @Patriot20233
    @Patriot20233 5 днів тому

    Thanks

  • @FuelTim
    @FuelTim 6 днів тому

    You saved me a ton of hassle with this - thank you!!!

  • @Kelly_Almond
    @Kelly_Almond 6 днів тому

    cool mode short cycle timer how to fix Goodman unit

  • @andrewbarnes7230
    @andrewbarnes7230 7 днів тому

    I work with these a bit. So i learned something !!!👍

  • @michaelg5070
    @michaelg5070 7 днів тому

    Thanks for the review. Im glad i watched this cuz im trying to reduce the weight in my bag so im glad i didnt order these.

  • @acrservicesmathewr7565
    @acrservicesmathewr7565 7 днів тому

    Use them all the time. Strong and durable

  • @rickschiaffo618
    @rickschiaffo618 8 днів тому

    Thank you

  • @elizwils3220
    @elizwils3220 9 днів тому

    We have 2 zones and around midnight, one side of the house continues to cool while the other side of the house stops cooling. Is there a reason one damper would close in the middle of the night while the other remains open?

    • @NighthawkHVAC
      @NighthawkHVAC 8 днів тому

      The thermostat in that zone may have a program that causes this to occur.

    • @elizwils3220
      @elizwils3220 8 днів тому

      ​@@NighthawkHVAC I am assuming it is because the damper closed but I am not certain. Last night I tried turning off the zone 2 that continued to cool to see if it would affect the other side but it didn't. The same side stayed warm (zone 1) and the air continued to come out forcefully on Zone 2 even though the thermostat was turned off.

    • @NighthawkHVAC
      @NighthawkHVAC 8 днів тому

      Then you may have a faulty damper actuator motor

  • @fistinyourface78
    @fistinyourface78 9 днів тому

    Thanks for video btw horrible technician

  • @keithswainston7144
    @keithswainston7144 9 днів тому

    Your that guy

  • @keithswainston7144
    @keithswainston7144 9 днів тому

    Piston is stuck reverse it a few times to try to break it free

  • @audiobrad99
    @audiobrad99 10 днів тому

    Interesting, but wish you had recorded the "before" sound.

  • @erekbush1498
    @erekbush1498 10 днів тому

    Clean those coils sheesh

  • @fazesenso2864
    @fazesenso2864 10 днів тому

    I wish you came out with more videos 😢

  • @hvacguy-h9c
    @hvacguy-h9c 10 днів тому

    I love that service checker... Once you learn how to use it well, it will be your biggest tool in Daikin service work.

  • @Kenpeters007
    @Kenpeters007 11 днів тому

    Does it work with the A2l ?

  • @Hvacnc
    @Hvacnc 11 днів тому

    Is there an indicator on the shaft part of the damper assembly that tells u if it’s open or close b4 u put the new one on? Like the shaft of a blower motor has a smooth side… is it like thay

    • @NighthawkHVAC
      @NighthawkHVAC 11 днів тому

      Nope. You just have to wing it. Sometimes I’ll just drill a hole in the damper assembly so I can see if it open or closed. Then I draw a line on the end of the shaft. If you’re lucky someone else marked it for you.

  • @Scott-hb8pu
    @Scott-hb8pu 12 днів тому

    I’ve thought about pulling the trigger on these

  • @yeyopedroza6594
    @yeyopedroza6594 12 днів тому

    so your telling me your operating the heat in medium speed? wont that overheat the system?

    • @NighthawkHVAC
      @NighthawkHVAC 12 днів тому

      Gas fired furnaces are factory set to low speed so medium is more than enough.

    • @yeyopedroza6594
      @yeyopedroza6594 12 днів тому

      @@NighthawkHVAC awesome! Thanks for clarifying

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 13 днів тому

    Those are 💩 💩 💩

  • @Scott-hb8pu
    @Scott-hb8pu 13 днів тому

    What model fieldpiece meter is that?

  • @ikkx
    @ikkx 13 днів тому

    How do you confirm whether it’s failed from outdoor board or indoor board?

  • @geoffreyyoung5419
    @geoffreyyoung5419 14 днів тому

    A waste of time you may have got the faulty compressor going but there is a good chance that it may burn out then you have a burn out too deal with just my thoughts

  • @austrianpainterhidingfromt5920
    @austrianpainterhidingfromt5920 14 днів тому

    Thank you for the video! I always enjoy your content. I'm especially grateful for any kind of mini split or inverter videos, I'm embarrassed to admit that those systems still confuse me sometimes.

  • @gingerstrand6153
    @gingerstrand6153 15 днів тому

    Seems those pumps fail often. Thanks for the video!!

  • @EverydayKindaGuy
    @EverydayKindaGuy 15 днів тому

    You're a horrible technician.

  • @TheBuckeyeBusinessman
    @TheBuckeyeBusinessman 15 днів тому

    How often do you need to replace?

  • @johnriff85
    @johnriff85 16 днів тому

    "this unit does not have pressure switches" pulls camera away to reveal pressure switch lmao In fairness I'm sure it's a fan cycle switch

  • @samjammal886
    @samjammal886 16 днів тому

    I would use my thermal imaging camera, but yeah according to the readings i think it's leaking internally, is there a full video on this ?

  • @user-wk1rh9pt6t
    @user-wk1rh9pt6t 16 днів тому

    my wednesday 12 ton coil change out was a 118 degree on the roof. my co-worker was suffering bad. he drinks soda, eats fast food, smokes weed and vapes. I was just fine, I don't drink soda, eat fast, or smoke. I barely broke a sweat. I used to have a hardtime with the heat unit I got my thyriod taken care of and changed my diet. I eat alot of eggs and meat. drinking just water. it changed my life. I don't get the hunger pains anymore and the 12 hour days are no issue.

  • @samjammal886
    @samjammal886 16 днів тому

    waiting on your videos explaining it champ

  • @mikecorral2358
    @mikecorral2358 17 днів тому

    Those magnet umbrellas are life savers

  • @TheIceman101
    @TheIceman101 19 днів тому

    Probably a dirty Water Condenser loop or inlet strainer.

  • @JammedFuzzball
    @JammedFuzzball 20 днів тому

    I have a strange one for you. My apartments AC unit has the normal drain line that leads outside, however under the handler there is a PVC that goes down, the connects sideways into a inch high pipe that has a black wire coming out of it, the drain leading outside is not stopped up yet that little pipe with the wire is dripping....wtf is it and what do I do to stop it?

  • @lordfarquad1735
    @lordfarquad1735 20 днів тому

    Don’t call it atomizing you nerd

  • @apendragon4057
    @apendragon4057 21 день тому

    where is the connect button to connect to the thermostat???

    • @NighthawkHVAC
      @NighthawkHVAC 19 днів тому

      You need a wireless adapter to hook up the wireless stats

  • @erixgar4117
    @erixgar4117 22 дні тому

    hey man how did you do ? did you pay out u pocket for the second PCB?

  • @kevinkrug466
    @kevinkrug466 22 дні тому

    Great fix

  • @mrpardesif16
    @mrpardesif16 23 дні тому

    Plz

  • @jmalmy2068
    @jmalmy2068 24 дні тому

    You did. I went back a few episodes and watched it. 🤙🏻

  • @AESOP2U
    @AESOP2U 25 днів тому

    Maybe use the studs from the old motor.

  • @Ahmed0824M
    @Ahmed0824M 26 днів тому

    Change out that mixing valve

  • @Iceblockjoe
    @Iceblockjoe 28 днів тому

    Don’t think it’s good to teach on a residential unit in a commercial application building will always be in a negative no outside air causes billions in energy costs

  • @wd8557
    @wd8557 28 днів тому

    I have one building at work that pulls water from the Detroit River. Fking zebra mussels get into the system and kills the water flow. I am slowly replacing those systems with mini-splits. Also their are no temp and pressure gauges, whoever installed those units were hacks.

  • @DelticEngine
    @DelticEngine 28 днів тому

    Why not use a thermal imaging camera to see what's going on?

  • @stevencossaboon3237
    @stevencossaboon3237 29 днів тому

    Nice work Nighthawk.

  • @eddiern
    @eddiern Місяць тому

    What will a loose belt cause the unit to do?

    • @NighthawkHVAC
      @NighthawkHVAC 28 днів тому

      It can cause the belt to wear out faster and/or break. It can also wear out the pulleys.